1. The fire control room must be on duty 24 hours a day, with no less than 2 people in each shift.
2. the daily management of the fire control room shall conform to the relevant requirements of the Maintenance and Management of Building Fire Control Facilities (GA587).
3. The fire control room shall ensure that the automatic fire alarm system and fire extinguishing system are in normal working condition.
4. The fire control room shall ensure sufficient water for fire water storage facilities such as high-level fire water tank, fire water pool and air pressure water tank; Ensure that the valves on the outlet pipe of the fire pump and the pipeline of the automatic sprinkler system are always open; Ensure that the switch of power distribution cabinet of fire-fighting electrical equipment such as fire pump, smoke exhaust fan and fire shutter is in the automatic (on) position.
5. after receiving the fire alarm, the fire control room must immediately confirm it in the fastest way.
6. after the fire is confirmed, the fire control room must immediately turn the fire alarm linkage control switch to the automatic state (unless it is in the automatic state), and at the same time dial the "119" fire alarm telephone.
7. The fire control room must immediately start the internal fire fighting and emergency evacuation plan of the unit and report to the person in charge of the unit at the same time.