A, automatic fire alarm system

Check the self-checking function of the fire alarm controller:

Check and record relevant measurable parameters, such as loop current;

Check the installation of smoke sensors and temperature sensors in public places, check whether they are in good contact with the base and whether the appearance is clean and intact;

Random sampling of at least 5% smoke or temperature each time, check whether the alarm is correct after spraying smoke or heating;

Manual alarm button, check whether the installation is firm, damaged or lost;

Randomly select at least 5% of manual alarm buttons at a time to simulate alarm and test whether the alarm function is normal;

Check the appearance of each module box in the floor to see if the external wiring is fixed properly;

The function of buttons on the linkage control cabinet is tested at the ratio of 10% every time, and the control function is normal.

Clean and dust the fire alarm control cabinet and linkage control cabinet. This thread is loose. It should be fastened. Check the self-check, mute and reset functions, switch the main power supply and standby power supply, and check the alarm.

Second, the fan and fire damper

Disconnect the main power supply, hang up the signboard and check whether the motor is well grounded.

Tighten loose screws and couplings in all parts.

Check the insulation resistance of the motor and the contacts of the main circuit.

Adjust the belt tightness, turn the pulley by hand, and observe whether the rotation is good.

Check and replace the gasket and sealing packing between the joint surfaces.

Clean the motor, air filter and the inside of the housing.

Lubricating oil is added to the rotating part to ensure the flexibility and stability of the coupling and bearing.

Check the mechanical opening and closing action and opening and closing angle sign of the regulating valve.

Manually start the machine to measure the three-phase current value, check the indicated voltage and ammeter, and listen to the operation sound of each part of the fan.

Check the control box (including the components in the box) of each remote control point comprehensively.

Stop the machine for three consecutive times, and check the correctness and reliability of manual remote control at each point.

Run continuously for 5-7 minutes to verify the normal operation of the fan.

Check the electrical contacts and terminals in each control box. If there are any burning imaginations, remove them and polish them with sandpaper. Tighten the terminals one by one with a screwdriver. Do not loosen the terminals.

Check the microswitch and internal terminal of the smoke exhaust valve. The terminal is not loose, and the microswitch is well fixed.

Check the reset button, guide wheel, steel wire and rotating shaft of the remote smoke exhaust valve, and oil the guide wheel, steel wire and rotating shaft with an oil pot. The reset button is controlled correctly and the smoke exhaust valve is opened flexibly.

Check the louver of each air supply outlet, and the louver of the air supply outlet is in the correct position.

Third, emergency lighting and evacuation indicator lights

The spare battery is turned on once every three months (half an hour), so that the battery can be discharged and recharged to prolong its life;

Check the glass panel of the exit indicator for scratches or cracks;

Whether the power indicator of export indicator lamp is on, if not, it should be repaired immediately;

Check whether the exit indicator lamp is installed firmly;

Remove and repair the defects found in the inspection, and then put them back in place;

Wipe the light box shell and panel clean.

Fourth,

It should be placed in a ventilated, dry and clean place, and should not be exposed to the sun, close to the heat source or subjected to severe vibration.

The ambient temperature of the suspension site is-10℃~55℃.

The location should be obvious, easy to access, and it will not affect the safe evacuation, and the passage between the cart type and its protected object should be unimpeded.

To check regularly, check the contents as follows:

(1) Whether the spray pipe is unblocked (if it is blocked, it should be unblocked in time);

(2) Whether the pressure gauge pointer is in the green area (if it is in the red area, check the reason and refill it after checking);

③ Whether the parts are complete (loose, deformed, corroded and damaged);

(4) Whether the anticorrosive coating of visible parts is in good condition (slight peeling should be repaired in time, and obvious corrosion should be sent to professional departments for maintenance and pressure test);

(5) Whether the lead seal is in good condition (once it is opened, it must be refilled in accordance with the regulations, and a sealing test should be conducted to reseal it).

Regular inspection and maintenance on time: once a quarter, check whether the nozzle and nozzle are blocked, corroded or damaged, whether the rigid connection nozzle can rotate around the axis and stay at any position, whether the cart-type driving mechanism is flexible and whether there are inspection marks. Sign the check card after inspection.

Filling is carried out by a professional company recognized by the fire department.

Five, indoor fire hydrant

External inspection of fire hydrant: check whether the fire hydrant door is closed properly, whether the lock and glass are damaged, and whether the seal of fire hydrant door is intact;

Randomly cancel the detection of 10% of the total number of fire hydrants, press the fire hydrant alarm button, and the fire center should have a correct alarm display to check whether the components in the box are in good condition, whether they fall off or not, and whether the faucet in the fire hydrant leaks;

Open the fire hydrant door and take out the hose, carefully check whether there is any damage, and repair or replace it if there is; Check whether there is blackening and mildew, if there is, take it out, brush it and dry it;

Replace the hose for folding or turning once;

Check whether the connection between water and hose connector is convenient and firm, and whether there are any defects. If there is, repair it immediately, then clean it and put it in the fire hydrant;

Check whether the interface gasket is intact, replace the aging leather gasket on the valve and oil the valve stem;

Check and trim all supports, repaint the painted parts and paint at the same time;

After the fire hydrant box is cleaned and the parts are stored neatly, lock the fire hydrant door and replace the inspection label card.

After the inspection, sign the fire box check card, put it into the fire box, and affix the seal of the fire box uniformly printed by the company.

Six, outdoor fire hydrant

Open the outdoor fire hydrant with a special fire hydrant wrench. The valve switch is required to be flexible and watertight.

Check the action sensitivity of the water flow indicator.

Check the terminals of the water flow indicator, and the contacts are free from looseness and corrosion.

Seven, automatic sprinkler system

Check the pressure gauge indication at the spray end of each layer once every quarter, test the signal indication of signal valve closing according to the ratio of 10%, and conduct water discharge test according to 30%. The fire center has a signal display.

Every quarter, the wet alarm valve and deluge valve are tested for water discharge, and the spray pump, rain pump or spray pump can be started, and the hydraulic alarm bell rings.

Check the nozzle once every quarter, and the surface is free of putty and leakage.

1/2 12 Last page

Eight, fire shutter

Start the lifting button of the fire shutter door, and the fire shutter door will rise steadily without blockage.

Check the electrical contacts and terminals in the control box. If the contact is burnt, remove it and polish it with sandpaper. Tighten the terminals one by one with a screwdriver, and do not loosen them.

Check the mechanical parts once a year, including gears and blades. If they are corroded, clean them with kerosene and then add lubricating oil to protect them.

Nine, emergency broadcast

Check the wiring and contacts of all switches and relays to ensure that the parts are complete, firm and in good contact, and the switches are flexible and reliable.

Adjust the volume controller to check whether the volume changes normally.

Check whether the volume and sound quality of microphone and microphone amplifier are normal.

Check whether the operation and sound quality of the tape drive or CD player are normal, which requires normal operation and good sound quality.

Check whether the switch of the floor call controller works normally, which requires flexibility and reliability.

X. internal telephone system

Check electrical contacts and terminals. If the contact is burnt, remove it and polish it with sandpaper. Tighten the terminals one by one with a screwdriver, and do not loosen them.

Check the call quality between the fixed telephone, the jack and the host to ensure that the sound quality is clear and there is no noise.

Check whether the key of the host computer is stuck and whether the switch is in good condition. It is required that the key is not stuck and the switch is in good condition.

XI。 Linkage control cabinet

Check the power indicator light and various switches on the control cabinet to ensure that the power indicator light is normal and the switches are in the open or automatic state.

Check the electrical contacts in the control cabinet. If there is any burning damage, remove it and sand it with sandpaper. Contact requirements intact, no looseness.

Check the terminal blocks and terminal boards of all electrical components and fasten them one by one with a screwdriver. Terminal connection is firm, no burns.

Check the power and signal wires. If it is damaged, wrap it with insulating tape. If they get old, replace them.

Dust off the inside of the control cabinet with a brush and a leather tiger.

Twelve, gas fire extinguishing system

Check that the weighing device or pressure gauge of the gas cylinder indicates normal weight or pressure.

Check the solenoid valve, bottle head valve and distribution valve of the actuator. The valve has no leakage and is very sensitive.

The simulation test of air control box shows that the alarm and linkage control are normal.