The safety requirements are as follows:
1. No matter whether the fire extinguisher has been used or not, the cylinder should be subjected to water pressure test one by one. In addition, the fire extinguisher has been used, although it has not reached the specified time limit, but the appearance inspection shows that the cylinder body has bumped and the appearance quality of the weld does not meet the specified requirements, the hydraulic test should also be carried out.
2. The cylinder that has passed the water pressure test has a complete decal, but if some paint skin falls off, it should be repainted.
3. Cylinders (except water-type fire extinguishers) that pass the water pressure test shall be dried. Approved by the People's Republic of China and the Ministry of Public Security on March 1, 1995 and implemented on December 1, 1995, GA 95-1995.
Extended information:
If the fire extinguisher is found to have problems through functional inspection, it must be repaired by a maintenance unit with maintenance qualification, and the damaged parts, the cylinder shall be subjected to hydrostatic test, and the fire extinguishing agent and driving gas shall be refilled.
the maintenance unit must strictly implement the fire extinguisher scrapping system. Every five years and before refilling, the main pressure parts of the fire extinguisher, such as the head and cylinder, should be tested by water pressure, and only those who pass the test can continue to use it.
after the test, it should be dried in time, and the inner wall should be checked, and there should be no obvious corrosion. If the water pressure test is unqualified, it is not allowed to be repaired and used by welding. The fire extinguisher repaired by the maintenance department shall be marked with the approval of the fire supervision department, and marked with the name of the maintenance unit and the date of maintenance.