Article 10 According to the severity of employee's violations, it can be divided into serious, serious and general violations, which are first-class violations, second-class violations and third-class violations respectively.
Eleventh any of the following illegal acts is a serious illegal act (Class I illegal act):
1, no ticket operation (including work and no ticket operation; Booking work; After the ticket is cancelled, do not reapply for a working ticket to continue the operation; Fill in the switching operation ticket, but don't bring it to the scene. It is stipulated that working tickets and operation tickets may not be handled).
2. Standardized operation instructions were formulated during the operation, but they were not implemented according to the standardized operation instructions (except for projects that cannot be implemented on site).
3. Do not check the electricity and grounding according to the regulations. Do not check electricity or only check the power supply side before installing grounding wire or pushing grounding knife switch, and do not check the non-power supply side.
4. Do not use the electroscope with the corresponding voltage level to check the electricity, or use the non-contact method to check the electricity (except as stipulated in Article 4.3.3 of the safety regulations).
5. Use lifting equipment for forced lifting due to overload or overspeed, over-depression angle and elevation angle, and carry out lifting operations near live equipment, with insufficient safety distance and unsupervised.
6. Use small instruments instead of large ones.
7. During the period when the personnel on duty are seriously off duty.
8. There is no guardian at the work site to carry out operations (including the work guardian leaving the work site and not temporarily appointing a competent work guardian, which makes the site lose supervision).
9. When the members of the working class are still working or have not been completely evacuated from the work site, the working director will go through the formalities for ending the work.
10. Non-enterprise personnel who have not been examined by the safety supervision department of this unit are allowed to handle the working ticket formalities.
The main safety measures of the working ticket issued by 1 1. are incomplete; The person in charge of the work and the licensor blindly implement it and do not express their opinions.
12. The person in charge of on-site work and the work permit change the main safety measures without authorization, which has potential accidents.
13. After the work is finished, the equipment operation will be resumed without going through the formalities for ending the working ticket, and the trial operation will be carried out without going through the formalities as required.
14, the dispatcher gives dispatching orders to those who have no right to accept dispatching orders; The dispatcher accepts and executes dispatching orders issued by personnel who have no right to issue dispatching orders.
15, scheduling command is wrong or misreported.
16, it is agreed to stop sending electricity.
17, accident emergency repair failed to perform work permit procedures.
18, expanding the scope of work without authorization.
19. During the electrical switching operation of the substation, the master unlocking key was used without approval.
20. Five kinds of vicious accidents (on-load disconnector, live grounding wire, circuit breaker with grounding wire, straying into live interval, mistakenly boarding tower) and attempted misoperation.
2 1. Dismantle the "Five Preventions", alarm and protection devices of operating equipment at will without approval.
22. When executing an operation ticket, skip or omit the operation (an important item of the operation ticket).
23. The off-duty operators operate the equipment without permission.
24. Switching operation or overhaul operation is unsupervised, and "√" is not marked after one operation.
25, playing computer games in the monitoring background machine or five prevention background machine.
25, don't know the operation situation, stop the wrong feeder or send maintenance equipment by mistake.
26, pole work suddenly cut off the guide rail and ground wire method of pay-off. When someone is working on the pole, adjust or relax the stay (or temporary stay).
27, aerial work don't wear a seat belt, don't wear a helmet.
28, aerial work after transposition, lose your seat belt protection.
29, replace the pole Tara line, don't play temporary stay; When tightening the wire, step on the wire or stand on the inner corner of the wire.
30, erection of poles, in the case of permanent stay not all installed to dismantle temporary stay.
3 1, the line was overhauled due to power failure, and the grounding wires were not installed at both ends of the work area as required.
32. The personnel on duty to take safety measures (including grounding wire, etc. ) is seriously inconsistent with the working ticket or the actual situation on site. If the licensing procedures have been fulfilled, both parties will be recorded as violations.
33. When the staff is still at work, remove the grounding wire.
34, do not have the qualification of live working personnel for live working.
35, live work is not in accordance with the provisions, the use of insulating tools, shielding clothing.
36. Without taking corresponding safety technical measures, the equipment with important defects or no electrical error-proof function is directly transmitted.
37. Force employees to take risks in their homework.
38. Before the start of electrical work, the working director did not make safety disclosure (explaining the work site situation and safety matters that should be paid attention to to to to the members of the working class), did not fill in the safety ticket (except the standardized work instruction), and the operator worked blindly without knowing the live parts.
39. Driving after being drunk or giving the vehicle to a person without a driver's license.
40, other illegal acts by the provincial company or unit safety supervision departments identified as serious violations.
Article 12 Any of the following illegal acts is a serious illegal act (Class II illegal act):
1. Forge someone else's name to issue a working ticket, the working ticket issuer issues a blank working ticket or issues a working ticket beyond his authority, and the switching operation ticket and standardized operation instruction are not checked and signed as required, forging someone else's signature.
2. Non-working class members take part in field workers.
3, leaders and full-time staff at the scene found violations do not stop.
4. The 0.4KV working power cord does not hang the grounding wire as required.
5. Wrong grounding wire sequence and insufficient buried depth of grounding rod.
6, power transmission line power cleaning, unused standby protective rope.
7. No standardized operation instructions and operating procedures have been formulated for major repairs and minor repairs that are included in the annual and monthly maintenance plan.
8, large complex and dangerous work ahead of time don't look at the job site.
9. 1 10KV and above equipment maintenance failed to make maintenance plan and perform examination and approval procedures in advance.
10. Non-electrical operators or personnel without Grade III safety education are engaged in electrical operations, and those without special operation qualifications are engaged in special operations (such as live working, electric welding and lifting).
1 1. Hire or subcontract a construction (contracting) team that has not passed the qualification examination of the safety supervision department.
12. Conduct naked fire operations in places where fireworks and firecrackers are prohibited without approval.
13. Change the brake with a ventilation ticket.
14. When the dispatcher gives the dispatching order but fails to give the even number or give the order, it is not recorded as required.
15, the grounding wire and safety measures that need to be kept or the termination procedures have not been handled, and the working ticket is not recorded.
16. No measures were taken to prevent short circuit, grounding and electric shock when working on densely wired screens such as DC screens and old electric screens in the substation. (It should be a violation of Category II)
17. No construction safety responsibility letter was signed between the developer and the contractor.
18. During lifting, the hoisted equipment was not bound as required.
19, the auxiliary safety facilities on the job site are incomplete or not completely in line with the requirements of safety regulations.
20, the use of unqualified (including without inspection, more than the inspection cycle) safety instruments and rigger instruments.
2 1, judge the grounding phase difference with high voltage test pen.
22, high pressure test in the process of pressurization, don't shout booster.
23. When both ends of the high-voltage test equipment are not in one place, the other end is unguarded; After the test, the capacitance test sample was not completely discharged.
24. Inspectors and constructors operate the equipment without authorization, leaving maintenance materials, tools and clothes on the running equipment.
25. The working controller uses the working power supply at work to pull the random connector.
26. Driving a vehicle with defects in important safety components such as braking system, steering system and transmission system.
27. Passengers forced the driver to drive too fast or failed to stop the driver's illegal behavior.
28. homework after drinking and driving after drinking.
29, single patrol line engaged in pole climbing operations, single patrol equipment, engaged in other work.
30. If in doubt during operation, do not report to the dispatcher or the person in charge on duty, and change the operation without authorization.
3 1. During construction, the construction scheme is changed without the approval of the approver.
32. When lifting heavy objects, stay, walk or engage in other work under the hoisted objects.
33, all kinds of maintenance, construction, patrol, not in accordance with the provisions, the correct use and management of standard operation card, or risk analysis before work.
34, other illegal acts by the provincial company or unit safety supervision departments identified as serious violations.
Thirteenth any of the following illegal acts is a general illegal act (Class III illegal act):
1. The equipment licensed by the superior dispatcher runs or works without the permission of the superior dispatcher.
2. For the equipment with load limit ordered by the superior dispatcher, the lower dispatcher sends power without authorization.
3. For the operation that requires the permission of the superior dispatcher, no application was made to the superior dispatcher in advance, and the operation was not reported in time.
4. During the switching operation, do not simulate, sing or recite.
5, close the circuit breaker operation, less than the equipment on-site inspection to check its actual position.
6. Full-time guardians concurrently hold other jobs.
7. The grounding wire installed by the personnel on duty is not registered.
8. The successor fails to sign as required.
9. Close the circuit breaker with insulating rod or through transmission mechanism, and don't wear insulating gloves.
10, loading and unloading high-voltage insurance, do not wear eye protection glasses, insulating gloves, and do not stand on insulating mats (tables).
1 1, working on the live secondary circuit, not wearing clothes as required (such as short-sleeved clothes, chemical fiber flammable materials, etc. ) and do not use insulating tools.
12, entering the production plant, not wearing safety helmet as required, and the production personnel not wearing clothes as required.
13. When assembling and disassembling the low-voltage power cord, do not disconnect the power supply first.
14. Wipe the live low-voltage appliances, light bulbs and terminal boards in operation with a damp cloth.
15. Use air compressor without protective cover, over-pressure protection device and pressure monitoring.
16. Climb the fragile and dry branches and cut down the trees.
17, wear gloves to work on the drilling machine; Polishing an object using the side of a grinder; Use a grinder without a protective cover.
18, the work was interrupted the next day, the work permit was not returned, and the licensing procedures were not handled the next day. Interruption, transfer and termination procedures were not handled when the working ticket was executed.
19, accident emergency repair or emergency troubleshooting failed to go through the working ticket formalities for more than the specified time.
20. When the working controller changes, the working ticket issuer and the new working controller do not sign the working ticket separately.
2 1, the planned maintenance was postponed, and the formalities were not handled as required.
22, operation personnel on duty do not perform handover procedures and equipment inspection.
23, grounding or short circuit using winding method.
24. Replace the fuse with aluminum wire and copper wire.
25, cast, back protection linking piece (including comprehensive soft linking piece from the station) not checked.
26. Flammable, explosive and toxic substances are not managed according to regulations.
27, scaffolding, etc. Does not meet the requirements of safety regulations.
28. Safety instruments were not carefully checked before use.
29. Failing to equip and use labor insurance articles as required.
30, driving with DC oil supply method.
3 1, the low-voltage lines are disconnected, and the personnel on duty and the person in charge of the work can't prevent the working power used by the working class from being disconnected.
32. The power cord insulation of the instrument used is damaged and leaks.
33, pull, close the ac grounding knife switches, do not use insulation tools.
34. Use low-voltage circuit breakers and cable switches without insulation cover.
35. Short-circuit the current terminal without a short-circuit piece (wire), and wrap the short circuit at will.
36. When using a single-sided ladder at work, the clamping degree between the ladder and the ground is not appropriate (generally around 60 degrees), and there is no one to support it and no staff to move the ladder on it.
37. Transfer tools or other equipment accessories and materials by throwing.
38. Maintenance and test of 1 10KV and above low oil switch. During the opening and closing operation of the switch, there are still people on the switch body.
39. When using inclined ladders, the ladders are not equipped with protective ropes.
40. Please wear plastic flat shoes when working on the oil switch and transformer body.
4 1, mobile smoking in the production plant.
42, electric welding machine without protective cover, grounding wire, welding wire, power cord does not meet the requirements, do not wear goggles in operation.
43, not in accordance with the provisions, the storage of gas cylinders with residual pressure.
44. During the withstand voltage test, the withstand voltage time of the tested equipment does not need to be timed by a clock, and it is only estimated by feeling.
45, in the maintenance power line without leakage protector, portable leakage protection box is not installed.
46. When drilling holes in tiankeng or frozen soil, the hammer should wear gloves, and the brazing assistant should not wear a helmet or be located in front of the hammer trajectory.
47. The dispatcher gave the order not to exchange names, and the attendant stopped reciting the contents of the order (both sides violated the regulations).
48, maintenance, pre-test, inspection and other work, there is no final record at the scene.
49. In the absence of earthquake-proof measures, vibration work is carried out on the running board.
50, all the work is over, the working class does not clean up the job site.
5 1. After the secondary circuit wiring was changed during the work, the drawings were not modified and signed in time.
52. When the temporary load is connected to the secondary circuit of the operating voltage transformer, it is not controlled by the circuit breaker with fuse.
53, in the case of poor contact test protection grounding wire.
54, tester in the oil switch mechanism box directly with the method of hand top switch closing contactor switch closing.
55, maintenance work is not in accordance with the provisions, hanging signs.
56. Excavation of foundation pits and cable channels near residential areas or traffic roads, without fences, unreliable foundation pit coverage, and no red light warning hanging at night.
57. When erecting and dismantling poles, the distance of other personnel shall not exceed 1.2 times the height of poles except necessary staff.
58. Hang clothes in the control room and do things unrelated to work.
59. Relatives accompany their families to work in the main control room.
60. The vehicle did not carry a fire extinguisher or the fire extinguisher expired.
6 1, other illegal acts are recognized as general illegal acts by the safety supervision departments of provincial companies or units.